SIT Help

 

Starting with parameter set Q the file naming

Convention has changed as follows.

 

First position

 

D – Domestic

H – Hydronic

P – Pool

C – Companion

 

Positions 2-5

Model number of unit

 

Position 6

indicates heat exchanger size

see chart below

 

Position 7

Letter version of parameter

 

Position 8

Lead or Lag

0-5

 

As an example an HWD 599  lag2 boiler

would have this file loaded.

 

H0599GQ2. 

 

Heat exchangers sizes

3+1 = A

4+1 = B

5+1 = C

6+3 = D

7+3 = E

10+6 = F

15 +8 = G

3 x1 8 = J

3 x 24 =K   

 

To determine the size or your heat exchanger look at column #1 for the first six numbers of your serial number, then under the heat exchanger column find the size. The chart above will give you the character associated with that size.

 

 

 

 

 

 

 First 6 numbers of serial number

79

Heat exchanger

 

031-145

 

 EVO79.8

3+1

031-145-006-02-08 is first 3+1

031-146

 

EVO79A

4+1/3+1

always 4+1 up to 031-146-001-46-07

031-147

 

EVO79 HWH H-st

4+1/3+1

031-147-021-48-07 is first 3+1

 

 

 

 

 

 

 

129

 

 

031-121

 

Hamilton EVO129.1 HWD ASME

4+1

always 4+1

031-122

 

Hamilton EVO129A HWD ASME / H-stamped

4+1

always 4+1

051-134

 

Hamilton EVO129.8 HWH

4+1

always 4+1

031-123

 

EVO129.8 HWH first 3+1 / 031-123-001-48-07

3+1

always 3+1

031-165

 

EVO129A

3+1

always 3+1

031-127

 

EVO129 HWD H-st.

3+1

always 3+1

031-128

 

EVO129 HWH H-st.

3+1

always 3+1

031-129

 

EVO129A HWH H-st.

4+1

always 4+1

031-159

 

EVO129.1 HWH design

4+1

always 4+1

 

 

 

 

 

 

 

179

 

 

031-135

 

Hamilton EVO179.8 HWH

4+1/5+1

031-135-038-17-06 is first 5+1

031-136

 

Hamilton EVO179.1 HWH ASME

5+1

always 5+1

031-137

 

Hamilton EVO179A HWH ASME / H-stamped

4+1/5+1

031-137-009-48-07 is first 5+1

031-153

 

EVO179 HWH H-stamped

4+1

always 4+1

031-130

 

EVO179A

4+1/5+1

always 4+1 up to 031-130-002-48-07

 

 

 

 

 

 

 

199

 

 

031-124

 

Hamilton EVO199A HWD ASME / H-stamped

6+3

always 6+3

031-131

 

Hamilton EVO199A HWH ASME / H-stamped

6+3

always 6+3

031-138 

 

Hamilton EVO199A HWHZ ASME / H-stamped

6+3

always 6+3

031-148 

 

EVO199 HWD H-st

5+1

always 5+1

031-149

 

EVO199.8

5+1

always 5+1

031-150

 

EVO199.1 HWD design

5+1

always 5+1

031-151

 

EVO199 HWH H-st

5+1

always 5+1

031-166

 

 EVO199A

5+1

always 5+1

 

 

 

 

 

 

 

299

 

 

031-141 

 

EVO299A (7+3) H-st

7+3

always 7+3

031-143 

 

EVO299A HWD H-st (6+3)

6+3

always 6+3

031-144

 

EVO299A HWD H-st (6+3)

6+3

always 6+3

031-152

 

EVO299 HWHZ H-st (6+3)

???

probably always 6+3

 

 

 

 

 

 

 

399

 

 

031-125 

 

Hamilton EVO399A HWD ASME / H-stamped

10+6

always 10+6

031-132

 

Hamilton EVO399A HWH ASME / H-stamped

10+6

always 10+6

031-139 

 

Hamilton EVO399A HWHZ ASME / H-stamped

10+6

always 10+6

031-167

 

EVO399A (10+6) H-st

10+6

always 10+6

 

 

 

 

 

 

 

599

 

 

031-126 

 

Hamilton EVO599A HWD ASME / H-stamped

15+8

always 15+8

031-133

 

Hamilton EVO599A HWH ASME / H-stamped

15+8

always 15+8

031-140

 

Hamilton EVO599A HWHZ ASME / H-stamped

15+8

always 15+8

031-168

 

EVO599A (15+8) H-st

15+8

always 15+8